Sign In | Join Free | My himfr.com
Home > VFD Variable Frequency Drive >

Water Pump Vfd Ac Drive , Frequency Inverter Drive Compact Structure

    Buy cheap Water Pump Vfd Ac Drive , Frequency Inverter Drive Compact Structure from wholesalers
     
    Buy cheap Water Pump Vfd Ac Drive , Frequency Inverter Drive Compact Structure from wholesalers
    • Buy cheap Water Pump Vfd Ac Drive , Frequency Inverter Drive Compact Structure from wholesalers

    Water Pump Vfd Ac Drive , Frequency Inverter Drive Compact Structure

    Ask Lasest Price
    Brand Name : Kinda
    Model Number : KD330
    Price : Negotiable
    Delivery Time : 3~8 Day
    Payment Terms : TT
    Supply Ability : Adequate inventory
    • Product Details
    • Company Profile

    Water Pump Vfd Ac Drive , Frequency Inverter Drive Compact Structure

    Water Pump VFD Variable Frequency Drive 3AC 380V 11KW ~ 18.5KW


    KD386 series constant pressure water supply


    When the pressure of the pressure transmitter is the largest, the frequency of the inverter is the lowest, and the speed of the pump motor is the lowest. When the pressure of the pressure transmitter is the smallest, the frequency of the inverter is the highest, and the speed of the pump motor is the highest. The frequency of the inverter changes with the change of water consumption. After the PID adjustment parameters are modified, the pipeline pressure is always kept constant; even if the water consumption is a variable, the final pressure is constant.


    1. Typical application diagram


    2.Parameters setting

    Function codeDefault valueSet valueDescription
    F0-0011Single pump system
    F0-010.4MPaCustomer set1. Please set it correctly based on requested pressure, the unit is MPa, 1MPa=10bar.
    2. Most of the family used systems, the pressure is 0.3~0.4MPa (3~4bar)
    F0-0280%Customer setWake up pressure; it is the percentage of F0-01.
    F0-0300It must be set as “0” while use 0~10V remote pressure gauge.
    1It must be set as “1” while use 4~20mA pressure transducer.
    F0-041.6MPa1.6MPa1. To set the maximum measure range of pressure transducer.
    2. It must be set correctly, otherwise it may cause pressure is inaccurate.

    ModelMotorRated Input Current (A)Rated Output Current (A)
    KWHP
    3AC 380V±15%
    KD386-01100T411152625
    KD386-01500T415203532
    KD386-01850T418.52538.537